KL3312 | 2-channel thermocouple input terminal with open-circuit recognition
The KL3312 analog input terminal allows thermocouples to be connected directly. The Bus Terminal is circuitry can operate thermocouple sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminals. The KL3312 can also be used for mV measurement.
Technical data | KL3312 |
---|---|
Number of inputs | 2 |
Power supply | via the K-bus |
Technology | 2-wire |
Thermocouple sensor types | types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement |
Connection method | 2-wire |
Measuring range | in the range defined in each case for the sensor (default setting: type K; -100…+1370 °C); mV measurement: ±30 mV…±120 mV |
Resolution | 0.1 °C per digit |
Conversion time | ~ 250 ms |
Wiring fail indication | yes |
Measuring error | < ±0.5 % (relative to full scale value) |
Electrical isolation | 500 V (K-bus/signal voltage) |
Current consumption power contacts | – (no power contacts) |
Current consumption K-bus | typ. 65 mA |
Bit width in the process image | input: 2 x 16 bit data (2 x 8 bit control/status optional) |
Configuration | no address setting, configuration via Bus Coupler or controller |
Weight | approx. 70 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Approvals | CE, UL, Ex |
Special terminals | |
---|---|
KL3312-0010 | type J |
KL3312-0011 | type J in Siemens S5 format |
KL3312-0012 | type L |
KL3312-0013 | type L in Siemens S5 format |
KL3312-0014 | type B |
KL3312-0015 | type B in Siemens S5 format |
KL3312-0016 | type E |
KL3312-0017 | type E in Siemens S5 format |
KL3312-0018 | type N |
KL3312-0019 | type N in Siemens S5 format |
KL3312-0020 | type R |
KL3312-0021 | type R in Siemens S5 format |
KL3312-0022 | type S |
KL3312-0023 | type S in Siemens S5 format |
KL3312-0024 | type T |
KL3312-0025 | type T in Siemens S5 format |
KL3312-0026 | type U |
KL3312-0027 | type U in Siemens S5 format |
KL3312-0028 | 0…120 mV measurement |
KL3312-0029 | type K in Siemens S5 format |
KL3312-0040 | expanded temperature range for type S and L type S: -50…+1700 °C (as supplied type L: -100…+900 °C) |
KL3312-0110 | type J, Fahrenheit scaling |
KL3312-2000 | setting of reference junction temperature via process image, unit 1/256° C in a 16 bit word |
KL3312-2100 | external reference point temperature specification via process image is possible, the unit is 1/256 °C in 16-bit format, fast conversion time 65 ms |
KL3312 Thermocouple input terminal - EL3312 Beckhoff
- AT2E
- Baumuller
- Bircher
- BCS Italy
- Bernard Control
- Beckhoff
- Beijer
- CS Instruments
- CEIA
- DECA WELD
- Elau Schneider
- Fireye
- Finetek
- Gastron
- IBA
- Insert Deal
- Knick
- Koganei
- Keofitt
- Keller - Its
- Kiepe Elektrik
- Kometer Flowmeter
- Lapar Valve
- Mark - 10
- Matsushima
- Minimax
- Nireco
- Ohkura
- Pavone Sistemi
- Pora
- Red lion
- Riels
- SOR
- Staubli
- TDK Lambda
- Teclock
- Vega
- YTC (Young Tech)
- Wago
- FOX THERMAL
- ORBINOX
- Clyde Pneumatic Conveying
- KREBS - RIEDEL
- PCI Instrument
- CEMB
- BARKSDALE
- INTORQ
- SITEC
- Spohn Burkhardt
- Emerson
- KSR KUEBLER
- Dosatec SA
- Thwing-Albert
- OKAZAKI
- TEK TROL
- NAGANO KEIKI
- Danh mục khác
-
Trực tuyến:3
-
Hôm nay:959
-
Tuần này:8722
-
Tháng trước:16766
-
Tất cả:1888246